Reference standard | : | IS/IEC 60898-1 ; IS/IEC 60947-2 |
Type or Series | : | C & D Curve |
No. of poles | : | 1 P, 1 P + N, 2 P, 3 P, 3 P + N, 4 P |
Rated current | : | 0.5 A, 1 A, 2 A, 3 A, 4 A, 5 A, 6 A, 10 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A |
Rated voltage | : | 240 V AC / 415 V AC |
Rated frequency | : | 50 Hz |
Rated short circuit eaking capacity | : | 10 kA - C Curve 10 kA - D Curve, ≤32 A 4.5 kA - D Curve, >32 A |
Magnetic release setting | : | (5-10) In - C Curve (10-20) In - D Curve |
Rated insulation voltage | : | 690 V |
Rated impulse voltage | : | 4 kV |
Dielectric strength | : | 2.5 kV |
Electrical or Mechanical endurance (no. of operations) minimum | : | 4000 |
Operating temperature | : | -5 °C to +55 °C |
Humidity | : | 95% RH |
Energy limit class | : | 3 |
Terminal capacity (maximum) | : | 35 mm² |
Tightening torque | : | 2 Nm |
Shock resistance | : | 40 mm free fall |
Protection class | : | IP 20 |
Positive contact indication | : | Yes, Through Flag Indication (Red-ON, Green-OFF) |
Positive contact indication | : | Yes, Through Flag Indication (Red-ON, Green-OFF) |
Net Weight or Pole | : | 125 g |
Dimensions (H x D x W) | : | 87.5 mm x 62 mm x 17.7 mm |
Mounting | : | Clip on DIN Rail (35 mm x 7.5 mm) |
Installation position | : | Vertical / Horizontal |
Case & Cover | : | Moulded, flame-retardant thermoplastic material |
Busbar connections top side | : | Pin Type |
Busbar connections bottom side | : | Pin / Fork Type |
Auxiliary contacts | : | Yes |
Shunt trip | : | Yes |